INSTALLATION INSTRUCTIONSAND USER GUIDEDIGITAL MODULATING ELECTRIC BOILERS & ELECTRIC COMBI BOILERSCMX15CM15FOR CENTRAL HEATING AND DOMESTIC HOT
9!!Typical Discharge Pipe terminations (source: Building Regulation G3) : !All installations must be fitted in accordance with all local regulations i
10!! WARNING THE SUPPLY CABLE TO THE BOILER SHOULD BE OF SUFFICIENT SIZE TO CARRY THE LOAD CAPACITY REQUIRED. IT SHOULD BE WIRED THROUGH A LINKED ISO
11!!5 COMISSIONING 5.1 LIMITING BOILER MAXIMUM OUTPUT The boiler is supplied for operation on maximum heat output of 15kW. The output can be rated b
12!!!* The standard configuration of the boiler only allows a maximum of 12kW when connected SINGLE-PHASE 230V – 50Hz. 5.2 HEATING SYSTEM INITIAL FILL
13!!5.4 HEATING SYSTEM FLUSHING CAUTION: Flush the heating installation thoroughly prior to installation. The heating system should be flushed in
14!!!MODELS CM15 !!!!!!!!!!!!!Push the button to start the boiler up. The same button will turn the boiler off when pushed again. If the heating or
15!!6.4 CENTRAL HEATING OPERATION First ensure that any external controls such as room thermostat or time clock are demanding heat. To select the he
16!!7 TROUBLESHOOTING 7.1 POSSIBLE FAULTS & SOLUTIONS Problem Possible cause Solution Boiler will not start No power to boiler. Check incoming
17!!!7.2 OVERHEAT LOCK-OUT & RE-SETTING Central heating overheat. If the boiler detects a overheat condition of 100ºC (80ºC if adapted floor hea
18!!8 MAIN COMPONENTS !!!!!!!!!!!!!!!!9 MAINTENANCE & CARE Gabarron electric boilers do not require any special maintenance for a prolonged and t
1!!INDEX 1 IMPORTANT 1 2 SAFETY 1 3 INTRODUCTION 2 3.1 DESIGN & OPERATION 2 3.2 PRINCIPLE COMPONENTS
19!!11 TECHNICAL DATA CMX15 CM15 Frequency Hz 50 50 Connection 3x400V+N~ ! ! Output limited to 15kW; Maximum intensity A 21.7 21.7 Output
20!! EC DECLARATION OF CONFORMITY According to ISO/CEI guide 22 and EN 45014 !!Manufacturer’s name: ELNUR S.A. Manufacturer’s address: ELNUR S.
21!!12 WIRING DIAGRAMS ! !
22!!NOTES ! The symbol on the product or in its packaging indicates that this pr
As a part of the policy of continuous product improvement Elnur reserves the right to alter specifications without notice. INSTALLATION INSTRUCTIONS A
2!!o All the models incorporate different safety elements. If one or more of them are activated, consult the section 7 TROUBLE SHOOTING. o In time,
3!! 1 Controls card. 2 ON / OFF switch. 3 Heating safety thermal limit switch. 4 Main electronic PCB. 5 Heating resistance. 6 Circulation pump. 7 Ins
4!!HOT WATER SYSTEM Competency to install unvented hot water system is required. Any existing system and controls (e.g. shower) must be suitable to op
5!!4.3 LOCATION WARNING INSTALL UPRIGHT ON A WALL SUITABLE TO SUPPORT THE TOTAL WEIGHT OF THE BOILER WHEN FULL OF WATER – 120 kg. The location shoul
6!!4.5 CLEARANCES A: 50 mm B: 10 mm C: 200 mm The clearances around the boiler as shown above must be observed for correct operatio
7!!Filling!loop!Always use assistance if required. Wear suitable cut resistant gloves when handling the appliance. Ensure safe lifting techniques are
8!!Cold Water Inlet A ½” connection is provided for connection to 15mm pipe. An integral isolating valve provides control of the incoming water suppl